27
INVERTER SETTING
4
4.4
Operation at Communication Error Occurrence
4.4.1
Operation selection at communication error occurrence (Pr. 500 to Pr. 502)
You can select operations at communication error occurrences by setting
Pr. 500 to Pr. 502
under network
operation.
(1) Waiting time for the communication option fault output after a communication error
Waiting time for the communication option fault output after a communication line error occurrence
can be set.
When a communication line error occurs and lasts longer than the time set in
Pr. 500
, it is recognized
as a communication option fault.
If the communication returns to normal within the time, it is not recognized as a communication option
fault, and the operation continues.
Parameter
Number
Name
Setting Range
Minimum Setting
Increments
Initial Value
500
Communication error
execution waiting time
0 to 999.8s
0.1s
0
Normal
Error
Pr. 500
setting time
Normal
Error
Communication line status
Communication option
fault (E.OP1)
Alarm signal (LF)
(
Pr. 502
= 3)
ON
Pr. 500
setting time
Recognition