29
INVERTER SETTING
4
(3) Inverter operation at a communication error occurrence
How the inverter operates at a communication line error or an option unit fault can be set.
About setting
z
Operation at an error occurrence
* When the communication returns to normal within the time period set in
Pr. 500
, the communication option fault (E.OP1)
does not occur.
z
Operation at error detection after elapse of
Pr. 500
time
Parameter
Number
Name
Setting Range
Minimum Setting
Increments
Initial Value
502
Stop mode selection at
communication error
0, 1, 2, 3
1
0
Error Definition
Pr. 502
Setting
Operation
Indication
Fault Output
Communication line
0
Continued *
Normal indication *
Not provided *
1
2
3
Communication
option itself
0, 3
Coast to stop
E. 1 lit
Provided
1, 2
Decelerated to stop
E. 1 lit after stop
Provided after stop
Error Definition
Pr. 502
Setting
Operation
Indication
Fault Output
Communication line
0
Coast to stop
E.OP1 lit
Provided
1
Decelerated to stop
E.OP1 lit after stop
Provided after stop
2
Not provided
3
Continued
Normal indication
Communication
option itself
0, 3
Coast to stop
E. 1 lit
Provided
1, 2
Decelerated to stop
E. 1 lit after stop
Provided after stop