30
INVERTER SETTING
z
Operation at error removal
Error Definition
Pr. 502
Setting
Operation
Indication
Fault Output
Communication line
0
Kept stopped
E.OP1 kept lit
Kept provided
1
2
Restart
Normal indication
Not provided
3
Continued
Communication
option itself
0, 3
Kept stopped
E. 1 kept lit
Kept provided
1, 2
CAUTION
• Communication line error [E.OP1 (fault data: HA1)] is an error that occurs on the communication line.
Communication option itself error [E. 1 (fault data: HF1)] is an error that occurs in the communication circuit
inside the option.
• Fault output indicates the fault signal (ALM signal) output and fault bit output.
• When the fault output setting is active, fault records are stored in the faults history.
When the fault output setting is not active, fault record is overwritten to the faults history temporarily but
not stored.
After the fault is removed, the fault indication is reset, changing the display back to normal, and the last
fault is displayed in the faults history.
• When the
Pr. 502
setting is "1" or "2", the deceleration time is the normal deceleration time setting (e.g.
Pr. 8,
Pr. 44, Pr. 45
).
• The acceleration time at a restart is the normal acceleration time setting (e.g.
Pr. 7, Pr. 44
).
• When the
Pr. 502
setting is "2", the operation/speed command at a restart is the one given before the fault
occurrence.
• When a communication line error occurs at the
Pr. 502
setting of "2", removing the error during deceleration
causes acceleration to restart at that point. (Acceleration is not restarted if the error is that of the option unit
itself.)