PPO TYPE SUPPORT SPECIFICATION
7.1
PROFIBUS profiles
The option unit operates as a "slave of the PROFIBUS DP master" or a "controller equivalent to
PROFIBUS DP master class 1 on an RS-485 network".
The PROFIBUS profile (data buffer) can be selected from among six different types, "PPO type1" to "PPO
type5", and "E5NP". This chapter expalins the profile of module type "PPO type1" to "PPO type5". (For the
module type "E5NP" profile, refer to
Chapter 8
Module type is changed with the slave module setting. For details, refer to
the instruction manual
of the
Network Master Configuration Software. The configuration of PPO type is as follows.
1 Word
PPO
type1
PPO
type2
PPO
type3
PPO
type4
PPO
type5
PKW
PZD
Module
type
PKE
IND
STW /
ZSW
HSW /
HIW
ECW /
ESW
Reserved Reserved Reserved Reserved Reserved Reserved Reserved
PWE
PKE
IND
STW /
ZSW
HSW /
HIW
PWE
Reserved Reserved Reserved
PKE
IND
STW /
ZSW
HSW /
HIW
PWE
ECW /
ESW
STW /
ZSW
HSW /
HIW
STW /
ZSW
HSW /
HIW
ECW /
ESW
Reserved Reserved Reserved
Input Data : 6 Words
Output Data : 6 Words
Input Data : 6 Words
Output Data : 6 Words
Input Data : 14 Words
Output Data : 14 Words
Input Data : 2 Words
Output Data : 2 Words
Input Data : 10 Words
Output Data : 10 Words