77
PPO TYPE NON-SUPPORT SPECIFICATION
8
8.8
Standard parameters
8.8.1 Normal parameter area (IND = 0200H (IND = 02H, PP = 00H))
You can use the PNU to make parameter settings from the network.
The table below lists PNU numbers corresponding to parameter numbers.
Standard parameter examples are introduced below. Refer to the examples and make parameter settings.
Refer to the inverter manual for details of the parameters.
Example of parameter list
IND
PNU
Parameter
Number
Name
Minimum
Setting
Increments
Setting Range
Decimal
Hexadecimal
0200
H
0H
0
Torque boost
0.1%
0 to 30
0 to 12C
1H
1
Maximum frequency
0.01Hz
0 to 120
0 to 2EE0
2H
2
Minimum frequency
0.01Hz
0 to 120
0 to 2EE0
3H
3
Base Frequency
0.01Hz
0 to 400
0 to 9C40
4H
4
Multi-speed setting (high speed)
0.01Hz
0 to 400
0 to 9C40
5H
5
Multi-speed setting (middle speed)
0.01Hz
0 to 400
0 to 9C40
6H
6
Multi-speed setting (low speed)
0.01Hz
0 to 400
0 to 9C40
···
···
···
···
···
···
CAUTION
•
Write to
Pr. 77
and
Pr. 79
is not allowed from the network with the FR-A7NP. (Read is allowed.)