PPO TYPE NON-SUPPORT SPECIFICATION
(2) Inverter status/operation command
The inverter status can be monitored and operation command can be given from the master.
IND
PNU
Item
0100H
AH
•
Inverter status
Refer to ZSW on
page 69
for details.
•
Run command
*1
Signal names are initial values. Using
Pr. 180 to Pr. 184
, you can change output signal functions. Refer to
the
inverter manual
for details of
Pr. 180 to Pr. 184
.
*2
Inverter reset function is invalid.
Bit
Name
Definition
1
Forward rotation command
(STF signal)
0: OFF (Stop command)
1: ON (Forward rotation
start)
A starting command is input to the
inverter when the signal turns ON.
A stop command is given when
both signals turn ON
simultaneously.
2
Reverse rotation command
(STR signal)
0: OFF (Stop command)
1: ON (Reverse rotation
start)
3
High-speed operation command
(terminal RH function)
Functions assigned to terminals RH, RM and RL are activated.
4
Middle-speed operation command
(terminal RM function)
5
Low-speed operation command
(terminal RL function)
7
Second function selection (RT signal)
1: Second function is selected
8
Terminal 4 input selection (AU signal)
1: Terminal 4 input is the main speed setting
10
Output stop (MRS signal)
Functions assigned to
Pr.183
is activated.
12
Inverter reset (terminal RES function)
Functions assigned to terminal RES is activated.
Other than
the above
−
Not used (0 is set)