1
1 INSTALLATION AND INSTRUCTIONS
*1
Models can be alternatively indicated with the inverter rated current (SLD rating).
*2
Specification differs by the type. Major differences are shown in the table below:
*3
Conforming to IEC60721-3-3 3C2/3S2.
*4
For the FR-A820-00340(5.5K)-R2R or higher, and the FR-A840-00170(5.5K)-R2R or higher
*5
Inverter equipped with a built-in Ethernet board (FR-A8ETH).
Type
Monitor output
Initial setting
Built-in EMC
filter
Control
logic
Rated
frequency
Pr. 19
"Base frequency
voltage"
FM
(terminal FM equipped
model)
Terminal FM:
pulse train output
Terminal AM: analog voltage output
(0 to
10 V DC)
OFF
Sink logic
60 Hz
9999
(same as the power
supply voltage)
CA
(terminal CA equipped
model)
Terminal CA:
analog current output
(0 to 20 mA DC)
Terminal AM: analog voltage output
(0 to
10 V DC)
ON
Source logic
50 Hz
8888
(95% of the power supply
voltage)
Notes
O
The rating plate shows the inverter rated current in SLD operation (Super Light Duty). The overload current rating at SLD is
110% of the rated current for 60 s and 120% for 3 s at surrounding air temperature of max. 40 °C.
O
In this Instruction Manual, the inverter model name consists of the applicable motor capacity and the rated current.
(Example: FR-A842-07700(315K)-R2R)
For further specification details like capacity, current or overload current rating refer to
O
In this installation guideline the following common designations are used for the different types of inverter models:
– FR-A8
m
0: Standard model
– FR-A8
m
2: Separated converter type
O
For selecting the right frequency inverter you should know details of your application and especially the load characteristic.
O
For how to read the SERIAL number, refer to
.
FR -
-
A8 0
2
-1
00046
-
R2R
Symbol
Voltage class
Symbol Structure, functionality
Capacity
*1
Description
Symbol Type
*2
Communica
-
tion type
Symbol Circuit board
coating
*3
Plated
conductor
2
200 V class
0
Standard model
00023 to
12120
Inverter SLD rated
current [A]
-1
FM
RS-485
Without
Without
Without
4
400 V class
2
Separated converter type
0.4 to 500K Inverter ND rated
capacity [kW]
-2
CA
-60
With
Without
-E1
FM
Ethernet
*5
-06
*4
With
With
-E2
CA
1.1 Inverter Type
Rating plate
Inverter model
Input rating
Output rating
Serial number
Country of origin
Symbol
Function
R2R
Roll to roll dedicated model
Inverter model
Serial number
Capacity plate