86
Frequency setting by external terminals
4.6.2
Jog operation (Pr. 15, Pr. 16)
(1) Jog operation from outside
When the JOG signal is on, a start and stop can be made by the start signal (STF, STR).
For the terminal used for Jog operation selection, set "5" in any of
Pr.178 to Pr.182 (input terminal function selection)
to assign
the function.
You can set the frequency and acceleration/deceleration time for jog operation. Jog operation can be performed in either
of the external and the PU operation mode.
This operation can be used for conveyor positioning, test operation, etc.
Parameter
Number
Name
Initial
Value
Setting Range
Description
15
Jog frequency
5Hz
0 to 400Hz
Frequency for jog operation.
16
Jog acceleration/
deceleration time
0.5s
0 to 3600s
Acceleration/deceleration time for jog operation. As the acceleration/
deceleration time, set the time taken to reach the frequency (initial
value is 50Hz) set in
Pr. 20 Acceleration/deceleration reference frequency
.
Acceleration/deceleration time can not be set separately.
These parameters are displayed as simple mode parameter only when the parameter unit (FR-PU04/FR-PU07) is connected. When the parameter unit is not
connected, the above parameters can be set when
Pr. 160 Extended function display selection
= "0".
Operation Display
1.
Screen at powering on
Confirm that the external operation mode is
selected. ([EXT] lit)
If not displayed, press
to change to the
external (EXT) operation mode. If the
operation mode still does not change, set
Pr.
79
to change to the external operation mode.
2.
Turn on the JOG switch.
3.
Turn the start switch (STF or STR) on.
The motor runs while the start switch (STF
or STR) is on.
The motor runs at 5Hz. (initial value of
Pr.
15
)
Rotates while ON
4.
Turn the start switch (STF or STR) off.
REMARKS
When you want to change the running frequency, change
Pr. 15 Jog frequency
. (initial value "5Hz")
When you want to change the acceleration/deceleration time, change
Pr. 16 Jog acceleration/deceleration time
. (initial value "0.5s")
The acceleration time and deceleration time cannot be set separately for jog operation.
Output frequency (Hz)
Pr. 20
Pr. 15 Jog frequency
setting range
Pr. 16
Forward
rotation
Reverse
rotation
ON
ON
ON
JOG signal
Forward rotation STF
Reverse rotation STR
Time
Three-phase AC
power supply
STF
Forward rotation
start
PC
10
2
5
Motor
Inverter
R/L
1
S/L
2
T/L
3
U
V
W
JOG signal
Reverse rotation
start
Connection diagram
for external jog operation
STR
RH (JOG)*
* When assigning the JOG signal to
the terminal RH
ON
JOG
Forward
rotation
Reverse
rotation
ON
Forward
rotation
Reverse
rotation
OFF
Stop
Summary of Contents for FR-D700 Series
Page 11: ...VII MEMO ...
Page 23: ...12 MEMO ...
Page 57: ...46 MEMO ...
Page 262: ...258 MEMO ...
Page 276: ...272 MEMO ...
Page 287: ...283 MEMO ...
Page 289: ......