98
Selection and protection of a motor
4.8.2
Applied motor (Pr. 71, Pr. 450)
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
(1) Set the motor to be used
Refer to the following list and set this parameter according to the motor used.
Setting of the used motor selects the thermal characteristic appropriate for the motor.
Setting is required to use a constant-torque motor. Thermal characteristic of the electronic thermal relay function
suitable for the motor is set.
When general-purpose magnetic flux vector is selected, the motor constants (SF-JR, SF-HR, SF-JRCA, SF-HRCA,
etc.) necessary for control are selected as well.
Parameter
Number
Name
Initial
Value
Setting Range
Description
71
Applied motor
0
0, 1, 3, 13,
23, 40, 43, 50, 53
Selecting the standard motor or constant-torque
motor sets the corresponding motor thermal
characteristic.
450
Second applied motor
9999
0, 1
Set when using the second motor.
9999
Second motor is invalid
(thermal characteristic of the first motor
(
Pr. 71
))
Pr. 71 (Pr. 450)
Setting
Thermal Characteristic of the Electronic Thermal Relay Function
Motor ( : Used motor)
Pr. 71
Pr. 450
Standard
(SF-JR, etc.)
Constant torque
(SF-JRCA, etc.)
0
(
Pr. 71
initial value)
Thermal characteristics of a standard motor
1
Thermal characteristics of the Mitsubishi constant-torque motor
40
—
Thermal characteristic of Mitsubishi high efficiency motor (SF-HR)
∗1
50
—
Thermal characteristic of Mitsubishi constant torque motor (SF-HRCA)
3
—
Standard motor
Select "Offline auto tuning
setting"
13
—
Constant-torque motor
23
—
Mitsubishi standard motor
(SF-JR 4P 1.5kW or less)
43
—
Mitsubishi high efficiency motor (SF-HR)
∗1
53
—
Mitsubishi constant-torque motor (SF-HRCA)
—
9999
(initial
value)
Without second applied motor
∗1
Motor constants of Mitsubishi high efficiency motor SF-HR.
∗2
Motor constants of Mitsubishi constant-torque motor SF-HRCA.
REMARKS
When performing offline auto tuning, set any of "3, 13, 23, 43, 53" in
Pr. 71
.
(Refer to
page
for offline auto tuning.)
For the FR-D740-120 and 160, the
Pr. 0
Torque boost
and
Pr. 12 DC injection brake operation voltage
settings are automatically
changed according to the
Pr. 71
setting as follows.
Automatic Change
Parameter
Standard Motor
Setting
Constant-torque Motor
Setting
Pr. 0
3%
2%
Pr. 12
4%
2%
∗1
Pr. 71
setting: 0, 3, 23, 40, 43
∗2
Pr. 71
setting: 1, 13, 50, 53
Summary of Contents for FR-D700 Series
Page 11: ...VII MEMO ...
Page 23: ...12 MEMO ...
Page 57: ...46 MEMO ...
Page 262: ...258 MEMO ...
Page 276: ...272 MEMO ...
Page 287: ...283 MEMO ...
Page 289: ......