108
Function assignment of external terminal and control
4.10 Function assignment of external terminal and control
4.10.1 Input terminal function selection (Pr. 178 to Pr. 182)
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
Purpose
Parameter that should be Set
Refer to Page
Assign function to input terminal
Input terminal function
selection
Pr. 178 to Pr. 182
Set MRS signal (output shutoff) to
NC contact specification
MRS input selection
Pr. 17
Assign start signal and forward/
reverse command to other signals
Start signal (STF/STR)
operation selection
Pr. 250
Assign function to output terminal
Output terminal function
assignment
Pr. 190, Pr. 192
Detect output frequency
Up-to-frequency
sensitivity
Output frequency
detection
Pr. 41 to Pr. 43
Detect output current
Output current detection
Zero current detection
Pr. 150 to Pr. 153, Pr. 166, Pr. 167
Remote output function
Remote output
Pr. 495, Pr. 496
Use these parameters to select/change the input terminal functions.
Parameter
Number
Name
Initial
Value
Initial Signal
Setting Range
178
STF terminal function
selection
60
STF (forward rotation command)
0 to 5, 7, 8, 10, 12, 14, 16, 18, 24,
25, 37, 60, 62, 65 to 67, 9999
179
STR terminal function
selection
61
STR (reverse rotation command)
0 to 5, 7, 8, 10, 12, 14, 16, 18, 24,
25, 37, 61, 62, 65 to 67, 9999
180
RL terminal function
selection
0
RL (low-speed operation command)
0 to 5, 7, 8, 10, 12, 14, 16, 18, 24,
25, 37, 62, 65 to 67, 9999
181
RM terminal function
selection
1
RM (middle speed operation
command)
182
RH terminal function
selection
2
RH (high-speed operation
command)
Summary of Contents for FR-D700 Series
Page 11: ...VII MEMO ...
Page 23: ...12 MEMO ...
Page 57: ...46 MEMO ...
Page 262: ...258 MEMO ...
Page 276: ...272 MEMO ...
Page 287: ...283 MEMO ...
Page 289: ......