110
Function assignment of external terminal and control
4.10.2 Inverter output shutoff signal (MRS signal, Pr. 17)
(3) Assign a different action for each MRS signal input from communication and external terminal
(
Pr. 17
= "4")
When
Pr. 17
is set to "4", the MRS signal from external terminal (output stop) can be changed to the normally closed (NC
contact) input, and the MRS signal from communication can be changed to the normally open (NO contact) input.
This function is useful to perform operation by communication with MRS signal from external terminal remained on.
The inverter output can be shut off by the MRS signal. Also, logic for the MRS signal can be selected.
Parameter
Number
Name
Initial Value
Setting Range
Description
17
MRS input selection
0
0
Normally open input
2
Normally closed input
(NC contact input specifications)
4
External terminal: Normally closed input
(NC contact input specifications)
Communication: Normally open input
The above parameters can be set when
Pr. 160 Extended function display selection
= "0". (
(1) Output shutoff signal (MRS signal)
Turning on the output shutoff signal (MRS) during inverter running shuts
off the output immediately.
Set "24" in any of
Pr. 178 to Pr. 182 (input terminal function selection)
to
assign a function to the MRS signal.
MRS signal may be used as described below.
(a) When mechanical brake (e.g. electromagnetic brake) is used to stop
motor
The inverter output is shut off when the mechanical brake operates.
(b) To provide interlock to disable operation by the inverter
With the MRS signal on, the inverter cannot be operated if the start
signal is entered into the inverter.
(c) Coast the motor to a stop.
When the start signal is turned off, the inverter decelerates the motor
to a stop in the preset deceleration time, but when the MRS signal is
turned on, the motor coasts to a stop.
(2) MRS signal logic inversion
(Pr. 17)
When
Pr. 17
is set to "2", the MRS signal (output stop) can be changed
to the normally closed (NC contact) input specification. When the MRS
signal turns on (opens), the inverter shuts off the output.
External MRS
Communication MRS
Pr. 17
Setting
0
2
4
OFF
OFF
Operation enabled
Output shutoff
Output shutoff
OFF
ON
Output shutoff
Output shutoff
Output shutoff
ON
OFF
Output shutoff
Output shutoff
Operation enabled
ON
ON
Output shutoff
Operation enabled
Output shutoff
REMARKS
The MRS signal can shut off the output, independently of the PU, external or network operation mode.
NOTE
Changing the terminal assignment using
Pr. 178 to Pr. 182 (input terminal function selection)
may affect the other
functions. Make setting after confirming the function of each terminal.
Parameters referred to
Pr. 178 to Pr. 182 (input terminal function selection)
ON
ON
MRS Signal
Time
STF (STR)
signal
The motor coasts to stop
Setting value "0"
Setting value "2"
(initial value)
Output stop
MRS
PC
Inverter
Output stop
MRS
PC
Inverter
Summary of Contents for FR-D700 Series
Page 11: ...VII MEMO ...
Page 23: ...12 MEMO ...
Page 57: ...46 MEMO ...
Page 262: ...258 MEMO ...
Page 276: ...272 MEMO ...
Page 287: ...283 MEMO ...
Page 289: ......