139
Operation setting at fault occurrence
4.13 Operation setting at fault occurrence
4.13.1 Retry function (Pr. 65, Pr. 67 to Pr. 69)
Retry operation automatically resets a fault and restarts
the inverter at the starting frequency when the time set in
Pr. 68
elapses after the inverter is tripped.
Retry operation is performed by setting
Pr.67
to any value
other than "0". Set the number of retries at fault
occurrence in
Pr. 67
.
When retries fail consecutively more than the number of
times set in
Pr. 67
, a retry count excess fault (E.RET)
occurs, resulting in inverter trip. (Refer to retry failure
example)
Use
Pr. 68
to set the waiting time from when the inverter
trips until a retry is made in the range 0 to 600s. (When the
setting value is "0s", the actual time is 0.1s.)
Reading the
Pr. 69
value provides the cumulative number
of successful restart times made by retry.
The cumulative count in
Pr. 69
is increased by 1 when a
retry is regarded as successful after normal operation
continues without faults occurring for more than five times
longer than the time set in
Pr.68
after a retry start.
(When retry is successful, cumulative number of retry
failure is cleared.)
Writing "0" to
Pr. 69
clears the cumulative count.
During a retry, the Y64 signal is on. For the Y64 signal,
assign the function by setting "64 (positive operation)" or
"164 (negative operation)" to
Pr.
190 or Pr. 192 (output
terminal fnction selection)
.
Purpose
Parameter that should be Set
Refer to Page
Recover by retry operation at fault
occurrence
Retry operation
Pr. 65, Pr. 67 to Pr. 69
Do not output input/output phase
failure alarm
Input/output phase failure
protection selection
Pr. 251, Pr. 872
If a fault occurs, the inverter resets itself automatically to restart. You can also select the fault for a retry.
When you have selected automatic restart after instantaneous power failure (
Pr. 57 Restart coasting time
≠
9999), restart
operation is performed at the retry operation time which is the same of that of a power failure. (Refer to
page
for the
restart function.)
Parameter
Number
Name
Initial
Value
Setting
Range
Description
65
Retry selection
0
0 to 5
A fault for retry can be selected.
(Refer to the next page)
67
Number of retries at fault
occurrence
0
0
No retry function
1 to 10
Set the number of retries at fault occurrence.
A fault output is not provided during retry operation.
101 to 110
Set the number of retries at fault occurrence. (The setting
value of minus 100 is the number of retries.)
A fault output is provided during retry operation.
68
Retry waiting time
1s
0.1 to 600s
Set the waiting time from when an inverter fault occurs
until a retry is made.
69
Retry count display erase
0
0
Clear the number of restarts succeeded by retry.
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
Retry failure example
Inverter output
frequency
Fault
occurrence
Fault
occurrence
Fault
occurrence
First retry
Second retry
Third retry
Retry failure
(E.RET)
ON
0
Fault signal
(ALM)
Pr. 68
Pr. 68
Pr. 68
Y64
ON
ON
ON
Inverter output
frequency
0
Y64
Pr. 68
Pr. 68
5
Retry success
Retry success example
Success count + 1
Time
ON
Fault occurrence
Retry success count
Retry start
Time
Summary of Contents for FR-D700 Series
Page 11: ...VII MEMO ...
Page 23: ...12 MEMO ...
Page 57: ...46 MEMO ...
Page 262: ...258 MEMO ...
Page 276: ...272 MEMO ...
Page 287: ...283 MEMO ...
Page 289: ......