141
Operation setting at fault occurrence
4.13.2 Input/output phase loss protection selection (Pr. 251, Pr. 872)
(1) Output phase loss protection selection
(Pr. 251)
When
Pr. 251
is set to "0", output phase loss protection (E.LF) becomes invalid.
(2) Input phase loss protection selection
(Pr. 872)
When
Pr. 872
is set to "1", input phase loss protection (E.ILF) is provided if a phase loss of one phase among the three
phases is detected for 1s continuously.
4.13.3 Earth (ground) fault detection at start (Pr. 249)
You can choose whether to make Input/output phase loss protection valid or invalid.
You can disable the output phase loss protection function that trips the inverter if one phase of the inverter output side
(load side) three phases (U, V, W) is lost.
The input phase loss protection function of the inverter input side (R/L1, S/L2, T/L3) can be made invalid.
Parameter
Number
Name
Initial Value
Setting Range
Description
251
Output phase loss
protection selection
1
0
Without output phase loss protection
1
With output phase loss protection
872
∗
Input phase loss protection
selection
1
0
Without input phase loss protection
1
With input phase loss protection
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
∗
Available only for the three-phase power input specification model.
NOTE
If an input phase loss continues for a long time, the converter section and capacitor lives of the inverter will be
shorter.
As phase loss is detected according to the bus voltage change, it can not be detected if the load is light. Unbalanced
phase-to-phase voltage of the three-phase power input may also be detected.
Phase loss can not be detected during regeneration load operation.
If parameter copy is performed from single-phase power input specification model to three-phase power input
specification model,
Pr. 872
setting may be changed. Check
Pr. 872
setting after parameter copy.
You can choose whether to make earth (ground) fault detection at start valid or invalid. Earth (Ground) fault detection is
executed only right after the start signal is input to the inverter.
Protective function will not activate if an earth (ground) fault occurs during operation.
Parameter
Number
Name
Initial Value
Setting Range
Description
249
Earth (ground) fault
detection at start
1
0
Without earth (ground) fault detection
1
With earth (ground) fault detection
The above parameters can be set when
Pr. 160 Extended function display selection
= "0".
NOTE
As detection is executed at starting, output is delayed for approx. 20ms every starting.
If an earth (ground) fault is detected with "1" set in
Pr. 249
, output side earth (ground) fault overcurrent (E.GF) is detected and
the inverter trips. (
If the motor capacity is smaller than the inverter capacity when using the FR-D740-120 or more, earth (ground) fault detection
may not be provided.
Summary of Contents for FR-D700 Series
Page 11: ...VII MEMO ...
Page 23: ...12 MEMO ...
Page 57: ...46 MEMO ...
Page 262: ...258 MEMO ...
Page 276: ...272 MEMO ...
Page 287: ...283 MEMO ...
Page 289: ......