191
Communication operation and setting
6
Inverter reset
Write
HFD
H9696: Inverter reset
As the inverter is reset at start of communication by the computer,
the inverter cannot send reply data back to the computer.
4 digits
(A, C/D)
H9666: Inverter reset
When data is sent normally, ACK is returned to the computer
and then the inverter is reset.
4 digits
(A, D)
7
Fault definition all
clear
Write
HF4
H9696: Faults history batch clear
4 digits
(A, C/D)
8
Parameter clear
All clear
Write
HFC
All parameters return to the initial values.
Whether to clear communication parameters or not can be
selected according to data. ( : Clear,
×
: Not clear)
for parameter clear, all clear, and communication
parameters.
When clear is executed for H9696 or H9966, communication-
related parameter settings also return to the initial values. When
resuming operation, set the parameters again.
Executing clear will clear the instruction code HEC, HF3, and HFF
settings. During password lock, only all parameter clear is
available with H9966 and H55AA.
4 digits
(A, C/D)
9
Parameter
Read
H00 to H63 Refer to the instruction code
and write and/or
read parameter values as required.
When setting
Pr. 100
and later, link parameter extended setting
must be set.
Data format of
Pr. 37
read and write is E2 and A2
4 digits
(B, E/D),
6 digits
(B, E2/D)
10
Write
H80 to HE3
4 digits
(A, C/D),
6 digits
(A2, C/D)
11
Link parameter
expansion setting
Read
H7F
Parameter description is changed according to the H00 to H09
setting.
For details of the settings, refer to the parameter instruction code
.
2 digits
(B, E1/D)
Write
HFF
2 digits
(A1, C/D)
12
Second parameter
changing
(instruction code
HFF = 1, 9)
Read
H6C
Setting calibration parameter
∗1
H00: Frequency
H01: Parameter-set analog value
H02: Analog value input from termin
∗1
Refer to the list of calibration parameters on the next page for
calibration parameters.
∗2
The gain frequency can also be written using
Pr. 125
(instruction code:
H99) or
Pr. 126
(instruction code: H9A).
2 digits
(B, E1/D)
Write
HEC
2 digits
(A1, C/D)
13
Multi command
Write/
Read
HF0
Available for writing 2 commands, and monitoring 2 items for
reading data (
for detail)
10 digits
(A3, C1/D)
14
Inverter type
monito
r
Inverter type
Read
H7C
Reading inverter type in ASCII code.
"H20" (blank code) is set for blank area
Example of FR-D740
H46, H52, H2D, H44, H37, H34, H30, H20 ..H20
20 digits
(B, E3/D)
Capacity
Read
H7D
Reading inverter capacity in ASCII code.
Data is read in increments of 0.1kW, and rounds down 0.01kW
increments
"H20" (blank code) is set for blank area
Example
0.4K ................. " 4" (H20, H20, H20, H20, H20, H34)
0.75K ............... " 7" (H20, H20, H20, H20, H20, H37)
6 digits
(B, E2/D)
No.
Item
Read/
Write
Instruction
Code
Data Definition
Number of
Data Digits
(Format)
Refer to
page 184
for data format (A, A1, A2, A3, B, C, C1, D, E, E1, E2, E3)
Clear Type
Data
Communication Pr.
Parameter clear
H9696
H5A5A
×
All parameter clear
H9966
H55AA
×