20
Control circuit specifications
(2) Output signal
(3) Communication
(4) Terminal for inverter manufacturer setting
NOTE
Set
Pr. 267
and a voltage/current input switch correctly, then input analog signals in accordance with the settings.
Applying a voltage with voltage/current input switch in "I" position (current input is selected) or a current with switch in
"V" position (voltage input is selected) could cause component damage of the inverter or analog circuit of output
devices.
Refer to page 145 for details.
Type
Terminal
Symbol
Terminal Name
Description
Rated Specifications
Reference
Page
Re
lay
A, B, C
Relay output (fault
output)
1 changeover contact output indicates that the inverter
protective function has activated and the output stopped.
Fault: discontinuity across B-C (continuity across A-C),
Normal: continuity across B-C (discontinuity across A-C)
Contact capacity:230VAC
0.3A
(power factor =0.4)
30VDC 0.3A
Open collector
RUN
Inverter running
Switched low when the inverter output frequency is equal to
or higher than the starting frequency (initial value 0.5Hz).
Switched high during stop or DC injection brake operation.
(Low indicates that the open collector output transistor is on
(conducts).
High indicates that the transistor is off (does not conduct).)
Permissible load 24VDC
(maximum 27VDC) 0.1A
(a voltage drop is 3.4V
maximum when the signal
is on)
SE
Open collector output
common
Common terminal of terminal RUN.
—
—
Analog
AM
Analog signal output
Select one e.g. output
frequency from monitor
items. Not output during
inverter reset.
The output signal is
proportional to the magnitude
of the corresponding
monitoring item.
Output item:
Output frequency (initial
setting)
Output signal 0 to
10VDC
Permissible load current
1mA
(load impedance 10k
Ω
or
more)
Resolution 8 bit
Type
Terminal
Symbol
Terminal Name
Description
Reference
RS-48
5
—
PU connector
With the PU connector, communication can be made through RS-485.
Conforming standard: EIA-485 (RS-485)
Transmission format: Multidrop link
Communication speed: 4800 to 38400bps
Overall length: 500m
Terminal Symbol
Description
S1
Keep these open. Otherwise, the inverter may be damaged.
Do not remove wires for shorting across terminal S1 and SC, across terminal S2 and SC. If one of these wires
is removed, the inverter cannot be operated.
S2
SO
SC