Monitor display and monitor output signal
Electronic thermal
relay function load
factor
0.1%
10
10
100%
Displays the thermal cumulative value on
the assumption that the thermal operation
level is 100% (Larger thermal between the
motor thermal and transistor thermal).
Output current peak
value
0.01A
11
11
Pr. 56
Holds and displays the peak value of the
output power monitor.
(Cleared at every start)
Converter output
voltage peak value
0.1V
12
12
200V class: 400V
400V class: 800V
Holds and displays the peak value of the
DC bus voltage value.
(Cleared at every start)
Output power
0.01kW
14
14
Rated drive unit
power
2
Displays the power on the drive unit output
side
Input terminal status
—
—
—
Displays the input terminal ON/OFF status
on the operation panel.
(
.)
Output terminal
status
—
—
Displays the output terminal ON/OFF
status on the operation panel.
(
.)
Cumulative
energization time
1h
20
—
Adds up and displays the energization time
after drive unit shipment.
You can check the numbers of the monitor
value exceeded 65535h with
Pr. 563
.
Reference voltage
output
—
—
21
—
Terminal FM:
Output 1440 pulse/s
Actual operation time
1h
23
—
Adds up and displays the drive unit
operation time.
You can check the numbers of the monitor
value exceeded 65535h with
Pr. 564
.
Can be cleared by
Pr. 171
.
Motor load factor
0.1%
24
24
200%
Displays the torque in percentage on the
assumption that the rated motor torque is
100%.
Cumulative power
0.01kWh
25
—
Adds up and displays the power amount
based on the output power monitor.
Can be cleared by
Pr. 170
.
PID set point
0.1%
52
52
100%
Displays the set point, measured value and
deviation during PID control (
for details.)
PID measured value
0.1%
53
53
100%
PID deviation
0.1%
54
—
Drive unit I/O terminal
monitor
—
55
—
Displays the ON/OFF status of the drive
unit input terminal and output terminal on
the operation panel (
for
details.)
Motor thermal load
factor
0.1%
61
61
Thermal relay
operation level
(100%)
Motor thermal heat cumulative value is
displayed.
(Motor overload trip (E.THM) at 100%)
Drive unit thermal
load factor
0.1%
62
62
Thermal relay
operation level
(100%)
Transistor thermal heat cumulative value is
displayed.
(drive unit overload trip (E.THT) at 100%)
PTC thermistor
resistance
0.01k
64
—
Displays the PTC thermistor resistance at
terminal 2 when PTC thermistor protection
is active.
(0.10k
to 31.5k
Types of Monitor
Unit
Pr. 52
Setting
Pr. 54
(FM)
Setting
Terminal FM
Full Scale Value
Description
Operation
panel
LED
PU
main
monitor