213
Communication operation and setting
Real time monitor
Refer to page 134
for details of the monitor description.
Use
Pr. 37
to set 1 increments, and use
Pr. 144
to set 0.01Hz increments. (
Pr. 37
and
Pr. 144
.)
Input terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, —: undetermined value)
Output terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, —: undetermined value)
The monitored values are retained even if a drive unit fault occurs. Resetting will clear the retained values.
b15
b0
—
—
—
—
—
—
—
—
—
RH
RM
RL
—
—
STR
STF
b15
b0
—
—
—
—
—
—
—
—
—
—
ABC
—
—
—
—
RUN
Register
Description
Unit
40201
Rotation speed/Machine speed/
Output frequency
1/1/0.01Hz
40202
Output current
0.01A
40203
0.1V
40205
Rotation speed setting/Machine
speed/Frequency setting
1/1/0.01Hz
40208
Converter output voltage
0.1V
40209
Regenerative brake duty
0.1%
40210
Electronic thermal relay function
load factor
0.1%
40211
Output current peak value
0.01A
40212
Converter output voltage peak value
0.1V
40214
Output power
0.01kW
40215
Input terminal status
—
40216
Output terminal status
—
40220
Cumulative energization time
1h
40223
Actual operation time
1h
40224
Motor load factor
0.1%
40225
Cumulative power
1kWh
40252
PID set point
0.1%
40253
PID measured value
0.1%
40254
PID deviation
0.1%
40261
Motor thermal load factor
0.1%
40262
Drive unit thermal load factor
0.1%
40263
Cumulative power 2
0.01kWh
40264
PTC thermistor resistance
0.01k
40277
32-bit cumulative power
(lower 16-bit)
1kWh
40278
32-bit cumulative power
(upper 16-bit)
1kWh
40279
32-bit cumulative power
(lower 16-bit)
0.01kWh
40280
32-bit cumulative power
(upper 16-bit)
0.01kWh
Register
Description
Unit