22
Control circuit specifications
2.3.3
Wiring of control circuit
(1) Standard control circuit terminal layout
(2) Wiring method
Wiring
Use a blade terminal and a wire with a sheath stripped off for the control circuit wiring. For a single wire, strip off the sheath of
the wire and apply directly.
Insert the blade terminal or the single wire into a socket of the terminal.
1) Strip off the sheath about the length below. If the length of the sheath peeled is too long, a short circuit may occur
among neighboring wires. If the length is too short, wires might come off.
Wire the stripped wire after twisting it to prevent it from becoming loose. In addition, do not solder it.
2) Crimp the blade terminal.
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is
inappropriate, or the face is damaged.
Refer to page 292
for the blade terminals available on the market.
Recommend wire size:
0.3mm
2
to 0.75mm
2
NOTE
Do not remove the shortening wires across the terminals S1 and SC and the terminals S2 and SC. Removing either
shortening wire disables the drive unit operation.
Wire stripping length
STF STR
PC
SD
RH
RM
RL
FM
C
B
A
10 2
5
4
RUN SE
S1 S2 SC
SO
SD
10mm
Crumpled tip
Wires are not inserted
into the sleeve
Unstranded
wires
Damaged
Wire
Wire
Sleeve
Sleeve
0 to 0.5mm
0 to 0.5mm
Summary of Contents for FR-D720-0.2K-G
Page 45: ...34 MEMO ...
Page 293: ...290 MEMO ...