Parameter list
Parameter list
64
Parameter List
Electr
onic ther
mal
O/L
rel
a
y
600
Free thermal reduction speed 1
0 to 12000r/min/
0 to 8000r/min
1r/min
9999
600
00
80
6
601
Free thermal reduction ratio 1
1 to 100%
1%
100%
601
01
81
6
602
Free thermal reduction speed 2
0 to 12000r/min/
0 to 8000r/min
1r/min
9999
602
02
82
6
603
Free thermal reduction ratio 2
1 to 100%
1%
100%
603
03
83
6
604
Free thermal reduction speed 3
0 to 12000r/min/
0 to 8000r/min
1r/min
9999
604
04
84
5
—
643
Voltage compensation amount setting
0 to 150%, 9999
1%
9999
643
2B
AB
6
—
658
Wiring resistance
0 to 5
, 9999
0.001
9999
658
3A
BA
6
—
665
Regeneration avoidance speed gain
0 to 200%
0.1%
100%
665
41
C1
6
Adjustment
function
672
Lq tuning target current adjustment
coefficient
50 to 150%, 9999
0.1%
9999
48
C8
6
702
Maximum motor speed
0 to 6000r/min/
0 to 4000r/min
1r/min
9999
702
02
82
7
706
Induced voltage constant (phi f)
0 to 5000mV/(s/rad),
9999
0.1mV/(s/rad)
9999
706
06
86
7
707
Motor inertia (integer)
10 to 999, 9999
1
9999
707
07
87
7
711
Motor Ld decay ratio
0 to 100%, 9999
0.1%
9999
711
0B
8B
7
712
Motor Lq decay ratio
0 to 100%, 9999
0.1%
9999
712
0C
8C
7
717
Starting resistance tuning
compensation
0 to 200%, 9999
0.1%
9999
11
91
7
721
Starting magnetic pole position
detection pulse width
0 to 6000
μ
s, 9999
0.1
μ
s
9999
721
15
95
7
724
Motor inertia (exponent)
4 to 7, 9999
1
9999
18
98
7
725
Motor protection current level
0 to 500%, 9999
0.1%
9999
725
19
99
7
726
Motor induced voltage constant (phi f)
exponent
0 to 2, 9999
1
9999
726
1A
9A
7
—
736
Electromagnetic brake interlock time
0 to 1s
0.01s
0s
736
56
D6
7
—
779
Operation speed during
communication error
0 to 12000/min/
0 to 8000r/min
, 9999
1r/min
9999
779
4F
CF
7
—
785
PM control torque boost
0 to 150%, 9999
0.1%
9999
785
55
D5
7
Acceleration/
deceleration
time
791
Acceleration time in low-speed range
0 to 3600s, 9999
0.1s
9999
791
5B
DB
7
792
Deceleration time in low-speed range
0 to 3600s, 9999
0.1s
9999
792
5C
DC
7
—
795
DC brake torque boost
0 to 150%, 9999
0.1%
9999
795
5F
DF
7
—
799
Pulse increment setting for output
power
0.1kWh, 1kWh, 10kWh,
100kWh, 1000kWh
0.1kWh
1kWh
799
63
E3
7
—
800
Control method selection
9, 30
1
30
800
00
80
8
Adjus
tmen
t
functio
n
820
Speed control P gain
0 to 1000%
1%
15%
820
14
94
8
821
Speed control integral time
0 to 20s
0.001s
0.333s
821
15
95
8
824
Torque control P gain (current loop
proportional gain)
0 to 200%, 9999
1%
9999
824
18
98
8
825
Torque control integral time (current
loop integral time)
0 to 500ms, 9999
0.1ms
9999
825
19
99
8
—
859
Rated PM motor current
0 to 500A, 9999
0.01A
9999
859
3B
BB
8
—
870
Speed detection hysteresis
0 to 150r/min/
0 to 100r/min
1r/min
15r/min
870
46
C6
8
Protecti
ve
functions
872
Input phase loss protection selection
0, 1
1
0
872
48
C8
8
Function
Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Parameter
Remarks
Instruction Code
Parameter
Read
Write
Extended
Copy
Clear
All Clear
Summary of Contents for FR-D720-0.2K-G
Page 45: ...34 MEMO ...
Page 293: ...290 MEMO ...