Basic settings
Simple mode parameter list
FR-D700 SC EC
5 - 17
Execution of tuning
When performing tuning or PU operation, press the RUN key of the operation panel or the FWD
or REV key of the parameter unit (FR-PU04/FR-PU07).
For external operation, turn on the run command (STF signal or STR signal). Tuning starts.
(Excitation noise is produced during tuning.)
b
CAUTION:
Before performing tuning, check the monitor display of the operation panel or
parameter unit (FR-PU04/FR-PU07) if the inverter is in the status for tuning. (Refer to
Tab. 5-4.) When the start command is turned on under V/f control, the motor starts.
NOTES
To force tuning to end, use the MRS or RES signal or press the STOP key of the operation
panel. Turning the start signal (STF signal or STR signal) off also ends tuning.
During offline auto tuning, only the following I/O signals are valid:
– Input terminal:
STF and STR
– Output terminal :
RUN, SO, AM, A, B, C
Note that the progress status of offline auto tuning is output from AM when speed and output
frequency are selected.
Since the RUN signal turns on when tuning is started, caution is required especially when a
sequence which releases a mechanical brake by the RUN signal has been designed.
When executing offline auto tuning, input the run command after switching on the main cir-
cuit power (R/L1, S/L2, T/L3) of the inverter.
Do not perform ON/OFF switching of the second function selection signal (RT) during execu-
tion of offline auto tuning. Auto tuning is not excecuted properly.
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......