Motor brake and stop operation
Parameter
6 - 82
Operation frequency setting (Pr. 10)
When the frequency at which the DC injection brake operates is set to Pr. 10, the DC injection
brake is operated when this frequency is reached during deceleration.
Operation time setting (Pr. 11)
Use Pr. 11 to set the duration period the DC injection brake is applied.
When the motor does not stop due to large load moment (J), increasing the setting produces an
effect.
When Pr. 11 = 0s, the DC injection brake is not operated. (At a stop, the motor coasts.)
Fig. 6-39:
When Pr. 11 is set to a value between 0.1
and 10s
I000007C
100
t
t
Output frequency [Hz]
DC injection br
ak
e
vo
lt
a
g
e
Pr. 10
Pr. 11
Pr. 12