Parameter
Selection of operation mode and operation location
FR-D700 SC EC
6 - 181
Switching of operation mode by external terminal (X16)
When external operation and operation from the operation panel are used together, use of the
PU-external operation switching signal (X16) allows switching betwen the PU operation mode
and external operation mode during a stop (during a motor stop, start command off).
When Pr. 79 = any of "0, 6, 7", the operation mode can be switched between the PU operation
mode and external operation mode. (Pr. 79 = 6 switch-over mode can be changed during op-
eration)
For the terminal used for X16 signal input, set "16" to any of Pr. 178 to Pr. 182 to assign the func-
tion.
Pr. 79
X16 Signal State Operation Mode
Remarks
ON (external)
OFF (PU)
0 (initial value)
External operation
mode
PU operation mode
Can be switched to external, PU or NET
operation mode
1
PU operation mode
Fixed to PU operation mode
2
External operation mode
Fixed to external operation mode (Can be
switched to NET operation mode.)
3 / 4
External/PU combined operation mode
External/PU combined mode fixed
6
External operation
mode
PU operation mode
Can be switched to external, PU or NET
operation mode with operation continued
7
X12 (MRS) ON
External operation
mode
PU operation mode
Can be switched to external, PU or NET
operation mode. (Output stop in external
operation mode.)
X12 (MRS) OFF
External operation mode
Fixed to external operation mode (Forcibly
switched to external operation mode.)
Tab. 6-39:
Operation mode switching by signal X16
NOTES
The operation mode status changes depending on the setting of Pr. 340 "Communication
start-up mode selection" and the ON/OFF states of the X65 and X66 signals. (For details,
refer to page 6-182).
The priorities of Pr. 79, Pr. 340 and signals are:
Pr. 79 > X12 > X66 > X65 > X16 > Pr. 340
Changing the terminal assignment using Pr. 178 to Pr. 182 may affect the other functions.
Please make setting after confirming the function of each terminal.
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......