Parameter
Special operation
FR-D700 SC EC
6 - 261
Output signal
Output terminal assignment during dancer control (PID control) operation
PID signal turns on during dancer control (PID control) or at a stop by PID control (in the status
PID operation being performed inside) (The signal is off during normal operation.)
For the terminal used for PID signal output, assign the function by setting "47 (positive logic) or
147 (negative logic)" in any of Pr. 190, Pr. 192 or Pr. 197.
PID monitor function
The PID control set point and measured value can be output to the operation panel monitor dis-
play and terminal AM.
For each monitor, set the following value in Pr. 52 "DU/PU main display data selection" and
Pr. 158 "AM terminal function selection".
Priorities of main speed command
The priorities of the main speed speed command source when the speed command source is
external are as follows:
JOG signal > multi-speed setting signal (RL/RM/RH/REX) > terminal 2.
The priorities of the main speed speed command source when "3" is set in Pr. 79:
Multi-speed setting signal (RL/RM/RH/REX) > set frequency (digital setting by PU, operation
panel).
Terminal 4 can not be selected as the main speed speed command even when AU terminal is
turned on.
Even when a remote operation function is selected by setting a value other than "0" in Pr. 59,
compensation of the remote setting frequency to the main speed is ignored (changes to 0).
NOTE
Changing the terminal function using any of Pr. 178 to Pr. 182, Pr. 190, Pr. 192 or Pr. 197
may affect the other functions. Make setting after confirming the function of each terminal.
Setting
Monitor
Description
Minimum
Increments
Terminal AM
Full Scale
Remarks
52
PID set point
0.1%
100%
—
53
PID measured
value
0.1%
100%
54
PID deviation
value
0.1%
—
Value cannot be output from the terminal AM.
The PID deviation value of 0% is displayed as
1000.
Tab. 6-93:
PID monitor function
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......