Common specifications
Appendix
A - 4
This operation guide is only available with option parameter unit (FR-PU07).
This protective function is available with the three-phase power input specification model
only.
This protective function does not function in the initial status.
When using the inverters at the ambient temperature of 40°C or less, the inverters can be
installed closely attached (0cm clearance).
The product may only be exposed to the full extremes of this temperature range for short
periods (e.g. during transportation).
FR-D700 SC
Specification
Display
Operation panel or
parameter unit
(FR-PU07)
Operating status
You can select from among output frequency, motor current (steady), output voltage,
frequency setting, cumulative energization time, actual operation time, converter output voltage,
regenerative brake duty, electronic thermal relay function load factor, output current peak value, ,
converter output voltage peak value, motor load factor, PID set point, PID measured value,
PID deviation, inverter I/O terminal monitor, output power, cumulative power, motor thermal load
factor, inverter thermal load factor, PTC thermistor resistance.
Fault definition
Fault definition is displayed when the protective function is activated,
the output voltage/current/frequency/cumulative energizing time right before the protection
function was activated and the past 8 alarm definitions are stored.
Interactive
guidance
Operation guide/trouble shooting with a help function
Protection
Protective functions
Overcurrent (during acceleration, deceleration or constant speed), overvoltage (during accelera-
tion, deceleration or constant speed), inverter protection thermal operation, motor protection
thermal operation, heatsink overheat, input phase failure
, output side earth (ground) fault over-
current at start
, output phase failure, external thermal relay operation
, PTC thermistor opera-
tion
, parameter error, internal board fault, PU disconnection, retry count excess
, CPU fault,
brake transistor alarm, inrush resistance overheat, analog input error, stall prevention operation,
output current detection value exceeded
, safety circuit fault
Warning functions
Fan alarm (FR-D720S-070SC or more, FR-D740-036SC or more), overcurrent stall prevention,
overvoltage stall prevention, PU stop, parameter write error, regenerative brake prealarm
,
electronic thermal relay function prealarm, maintenance output
, undervoltage, operation panel
lock, password locked, inverter reset, Safety stop function
Environment
Ambient temperature
−
10°C to +50°C (non-freezing)
Storage temperature
−
20°C to +65°C
Ambient humidity
Max. 90% (non-condensing)
Ambience conditions
For indoor use only, avoid environments containing corrosive gases, install in a dust-free location.
Altitude
Max. 1000m above sea level
Vibration resistance
Max. 5.9m/s² (JIS 60068-2-6) or less at 10 to 55Hz (directions of X , Y and Z axes)
Tab. A-3:
Common specifications (2)
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......