Parameter
Function assignment of external terminals
FR-D700 SC EC
6 - 101
Inverter operation ready signal (RY) and inverter running signal (RUN)
When the inverter is ready to operate, the output of the operation ready signal (RY) is on. It is
also on during inverter running.
When the output frequency of the inverter rises to or above Pr. 13 "Starting frequency", the out-
put of the inverter running signal (RUN) is turned on. During an inverter stop or DC injection
brake operation, the output is off.
When using the RY or RUN signal, set "11 (source logic)" or "111 (sink logic)" (RY) or "0 (source
logic)" or "100 (sink logic)" (RUN) to any of Pr. 190, Pr. 192 or Pr. 197 to assign the function to
the output terminal.
This signal turns OFF during power failure or undervoltage.
Output is shutoff under conditions such as a fault occurrence, MRS signal ON, and the safety
stop operation.
I001796E
Fig. 6-51:
Ready and motor running signals
Output
Signal
Start
Signal
OFF
(during
stop)
Start
Signal ON
(during
stop)
Start
Signal ON
(during
operation)
Under DC
Injection
Brake
Output
shutoff
Automatic Restart after
Instantaneous Power Failure
Coasting
Restart-
ing
Start
Signal ON
Start
Signal
OFF
RY
ON
ON
ON
ON
OFF
ON
ON
RUN
OFF
OFF
ON
OFF
OFF
OFF
ON
Tab. 6-16:
Output signal output
NOTE
The RUN signal (positive logic) is assigned to the terminal RUN in the initial setting.
Power supply
Output frequency
Starting frequency Pr. 13
DC injection brake operation
Time
DC injection brake operation point
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
Reset processing
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......