6.9.8
Remote output function (REM, Pr. 495, Pr. 496)
You can utilize the on/off of the inverter’s output signals instead of the remote output terminal of
the programmable logic controller.
The above parameters can be set when Pr. 160 = 0.
The above parameters allow its setting to be changed during operation in any operation
mode even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
The output terminal can be turned on/off depending on the Pr. 496 setting. The remote output
selection can be controlled on/off by computer link communication from the PU connector.
Set "96" (positive logic) or "196" (negative logic)" to any of of Pr. 190, Pr. 192 or Pr. 197, and as-
sign the remote output (REM) signal to the terminal used for remote output.
By setting "1", the output terminal turns on (off for sink logic). By setting "0", the output terminal
turns off (on for sink logic) (refer to Fig. 6-57).
Not assigned (always "0" when read).
Pr.
No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
495
Remote output
selection
0
0
Remote output data
clear at powering off
Remote output data
clear at inverter
reset
190/192/
197
Output terminal
function selection
1
Remote output data
retention at powering
off
10
Remote output data
clear at powering off
Remote output data
retention at inverter
reset
11
Remote output data
retention at powering
off
496
Remote output
data 1
0
0–4095
Example
쑴
When "96" (source logic) is set to Pr. 190 "RUN terminal function selection" and "1" (H01) is
set to Pr. 496, the terminal RUN turns on.
쑶
I002083E
Fig. 6-57:
Remote output data
Pr. 496
0
b
1
1
b
SO
ABC
RU
N
Summary of Contents for FR-D720S SC EC
Page 2: ......
Page 4: ......
Page 24: ...Description of the case Product checking and part identification 1 4 ...
Page 108: ...Operation panel Operation 4 20 ...
Page 436: ...Setting for the parameter unit and operation panel Parameter 6 286 ...
Page 484: ...Measurements on the main circuit Maintenance and inspection 8 14 ...
Page 504: ...Specification change Appendix A 20 ...
Page 505: ......
Page 506: ......
Page 510: ...Index Appendix A 24 ...
Page 511: ......