14
1
0
PU or network operation
Inverter operates in the network operation mode.
(Profibus master module need not be used for switching)
1
PU operation
Inverter operates in the PU operation mode.
2
Network operation
Inverter operates in the network operation mode.
(Profibus master module need not be used for switching)
3
External/PU combined
operation
Inverter operates in the external/PU combined operation mode.
Input running frequency from the PU and the start signal from outside.
4
External/PU combined
operation
Inverter operates in the external/PU combined operation mode.
Input running frequency from outside and the start signal from the PU.
6
Switch-over
Inverter operates in the network operation mode.
Operation mode is switched while running.
Refer to page 16 for details.
7
PU operation interlock
MRS signal ON .......... Inverter operates in the network operation mode.
(Operation mode can be switched to the external
operation mode by the program.)
MRS signal OFF ........ Inverter operates in the external operation mode.
8
Operation mode switch-
over by the external signal
X16 signal ON............ Inverter operates in the network operation mode.
(Operation mode can be switched to the external
operation mode by the program.)
X16 signal OFF.......... Inverter operates in the PU operation mode.
Pr. 340
Setting
Operation Mode
Mode at Power On or at Restoration
from Instantaneous Power Failure
Pr. 79