15
When "0" or "6" is set in Pr. 79 when Pr. 340 = "10", the operation can be switched between the PU
operation and the network operation from the operation panel or the parameter unit (FR-PU04).
• Operation panel
Use
display on the operation mode switching menu to change the operation mode to the PU
operation mode and
display to the network operation mode.
• FR-PU04
Use
to change the operation mode to the PU operation and
to the network operation.
Pr. 340
Setting
Operation Mode
Mode at Power On or at Restoration
from Instantaneous Power Failure
Pr. 79
10
0
PU or network operation
Inverter operates in the network operation mode.
Operation mode can be switched between the PU operation and the
network operation.
1
PU operation
Inverter operates in the PU operation mode.
2
Network operation
Inverter operates in the network operation mode.
3
External/PU combined
operation
Inverter operates in the external/PU combined operation mode.
Input running frequency from the PU and the start signal from outside.
4
External/PU combined
operation
Inverter operates in the external/PU combined operation mode.
Input running frequency from outside and the start signal from the PU.
6
Switch-over
Inverter operates in the network operation mode.
Operation mode can be switched between the PU operation and the
network operation.
7
PU operation interlock
MRS signal ON .......... Inverter operates in the external operation mode.
(Operation mode can be switched to the PU
operation mode by the parameter unit.)
MRS signal OFF ........ Inverter operates in the external operation mode.
8
Operation mode switch-
over by the external signal
X16 signal ON............ Inverter operates in the external operation mode.
X16 signal OFF.......... Inverter operates in the PU operation mode.