Profibus PROFILES—PPO Support Specification
PZD STW
-
0 to 2
Not used (1 is set)
Control
enable
3
0: Inverter output shutoff
1: Inverter output shutoff is cancelled
-
4 to 6
Not used (1 is set)
Fault
reset
7
[At inverter error]
0: No action
1: Inverter reset (error reset)
[When inverter is normal]
No action
-
8 to 9
Not used (0 is set)
PZD
enable
10
0: Command request of PZD is not processed.
(*1)
1: Command request of PZD is processed.
• At power-on or inverter reset, set 1 once.
STF
signal
11
0: OFF
1: ON (Forward rotation command)
STR
signal
12
0: OFF
1: ON (Reverse rotation command)
-
13
Not used (0 is set)
MRS
terminal
14
0: MRS-OFF
1: MRS-ON (Output shutoff)
Functions are changed depending on the Pr.183 setting. However, do not change the
factory-set value
"
6
"
.
RAM/
E
2
PROM
15
0: Set frequency (HSW) is written to RAM (Power-on reset returns the changed set
frequency to the setting before it was written to RAM.).
1: Set frequency (HSW) is written to E
2
PROM.
*2 PZD enable and command count request can be executed.
Name
Bit
Description