Assign IP Address
FR-E800-EPA:
192.168.3.5
NZ2GNSS2-16DTE:
192.168.3.10
KEY NOTE: You MUST use IP address in addition to Network / Station #
BOTH are required for proper communications
Set Communication Speed
NZ2GNSS2-16DTE (Class B 1Gbps) : “
Basic Speed
”
FR-E800-ESC-EPA (
Class A 100Mbps
): “
Low Speed
”
Note: we MUST use “Low Speed” because Master module is set to 1Gbps. The
“Basic Period” would be too fast for the E800.
Basic Period: Fastest Communication Speed
Normal-Speed: Divide Basic by x4
Low-Speed: Divide Basic by x16 (i.e. 1000us x 16 = 16,000us = 16ms)
E800 requires 5000us or slower