INVERTER SETTING
(2) Operation mode switching by the PU operation interlock signal (X12)
PU operation interlock is a function that forcefully changes the operation mode to the Network operation
mode at turn-OFF of the X12 signal (Bit 11), which gives operation commands through FL remote
communication.
This function prevents the operation mode from being accidentally unswitched from the PU operation
mode. If the operation mode left unswithced from the PU operation mode, the inverter does not reply to the
commands sent through FL remote communication.
X12
signal
Function/Operation
Operation mode
Parameter write
ON
Operation mode (PU, NET) switching is enabled
Output stop during Network operation
Parameter write is enabled (depending on
Pr. 77
Parameter write selection
and each parameter write
conditions. Refer to the
Inverter Manual
for details.)
OFF
Forcibly switched to Network operation mode
Network operation is enabled
Switching to the PU operation mode is disabled
Parameter write is disabled
(Note that the
Pr.297
setting is available
when
Pr.296
≠
"9999.")
REMARKS
• This function is available for the inverters with the SERIAL numbers on
page 5
.