84
<Link status>
<Higher-layer status>
The inverter periodically creates "higher layer status" based on "slave control status of FL remote" and
"inverter status". In addition, the inverter reports the "higher layer status" to the master (FA link layer)
periodically.
b7
b6
b5
b4
b3
0
0
b2
b1
b0
Node status 0: Disconnect, 1: Participate
Communication invalid is detection 0: Undetected, 1: Detected
Higher layer operation signal 0: Normal, 1: Error
Common memory data 0: Invalid, 1: Valid
Common memory setting 0: Uncompleted, 1: Completed
Address duplication 0: Undetected, 1: Detected
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Error information
00: NORMAL (Without inverter error)
01: WARNING (Alarm occurrence)
10, 11: ALARM (Inverter error has occurred)
Operation information
0: STOP (Slave control status of FL remote is not operating)
1: RUN (Slave control status of FL remote is operating)
Not used