110
(3) CC-Link extended setting
(Pr. 544)
The functions of the remote register can be extended. Refer to
page
for the details of the remote I/O signals and the
remote registers.
The program used for the conventional inverter series (FR-A5NC) can be used.
The upper 8 bits of RWw2 are not used for the link parameter extended setting.
When using the double setting of the CC-Link Ver.2, station data of the master station must be set to double.
(If the master station is CC-Link Ver.1, this setting is not available. )
(4) I/O signal list
1)Remote I/O signals (32 points) (For details, refer to
page
("n" indicates a value determined by the station number setting. )
These signals are set in the initial setting. Using
Pr. 3 to Pr. 7
, input signals assigned to the device numbers can be changed.
For the available signals, refer to
page 76
.
These signals are set in the initial setting. Using
Pr. 11 to Pr. 16
, output signals assigned to the device numbers can be changed.
For the available signals, refer to
page 78
.
Output of the error status flag signal depends on the retry function setting.
Pr. 544
Setting
Description
CC-Link Ver.
0 (Initial setting)
1
Occupies one station (FR-A5NC compatible)
1
Occupies one station
12
2
Occupies one station, double setting
REMARKS
The setting becomes valid after converter reset. (Refer to
page
for the converter reset
.
)
Device
No.
Signal
Device No.
Signal
RYn0
Not used
RXn0
Not used
RYn1
Not used
RXn1
Not used
RYn2
Converter stop (terminal SOF function)
RXn2
Converter ready (inverter run enable signal)
RYn3
Monitor switching (terminal X1 function)
RXn3
Converter reset(terminal RSO function)
RYn4
Monitor switching (terminal X2 function)
RXn4
During converter run(terminal CVO function)
RYn5
Converter reset (terminal RES function)
RXn5
Overload alarm(terminal Y1 function)
RYn6
ROH inrush resistance overheat detection
(terminal ROH function)
RXn6
Power supply phase detection(terminal Y2
function)
RYn7
Not used
RXn7
Output voltage match (terminal Y3 function)
RYn8
Not used
RXn8
Fault(terminal ABC function)
RYn9
Not used
RXn9
Not used
RYnA
Not used
RXnA
Not used
RYnB
Not used
RXnB
Not used
RYnC
Monitor command
RXnC
Monitoring
RYnD
Not used
RXnD
Not used
RYnE
Not used
RXnE
Not used
RYnF
Instruction code execution request
RXnF
Instruction code execution completion
RY(n+1)0 to
RY(n+1)7
Reserved
RX(n+1)0 to
RX(n+1)7
Reserved
RY(n+1)8
Not used
(initial data process completion flag)
RX(n+1)8
Not used
(initial data process request flag)
RY(n+1)9
Not used
(initial data process request flag)
RX(n+1)9
Not used
(initial data process completion flag)
RY(n+1)A Error reset request flag
RX(n+1)A
Error status flag
RY(n+1)B
to
RY(n+1)F
Reserved
RX(n+1)B
Remote station ready
RX(n+1)C
to
RX(n+1)F
Reserved
HC2.book 110 ページ 2012年11月19日 月曜日 午前10時52分