148
Rated specifications
6.1 Rated specifications
200V
400V
Model name of the 400V class ends with H.
The permissible voltage imbalance ratio is 3% or less. (Imbalance ratio = (highest voltage between lines - average voltage between three lines ) / average
voltage between three lines
100)
DC output capacity when the input voltage is 200VAC (400V for the 400V class)
Change the MC power supply stepdown transformer tap according to the input voltage.
(Refer to page 51)
The % value of the overload current rating indicates the ratio of the overload current to the converter's rated input current. For repeated duty, allow time for
the converter and the inverter to return to or below the temperatures under 100% load.
The protective structure is IP40 for FR-DU07-CNV (except the PU connector) and IP00 for the outside box (220K or lower) and the reactor regardless of
their capacities.
When the hook of the converter front cover is cut off for installation of the plug-in option, the protective structure changes to the open type (IP00).
Mass of FR-HC2 alone.
Model name
FR-HC2-
K
7.5
15
30
55
75
Applicable inverter capacity (kW)
7.5
15
30
55
75
Rated output capacity (kW)
10.7
19.8
38
71
92
Rated input voltage (V)
Three-phase 200V to 220V 50Hz/200V to 230V 60Hz
Rated input current (A)
33
61
115
215
278
Overload current rating
150% 60s
Permissible power supply voltage fluctuation
170V to 242V 50Hz
170V to 253V 60Hz
170V to 230V
50Hz/60Hz
Permissible power supply frequency fluctuation
5%
Input power factor
0.99 or more (when load ratio is 100%)
Power supply capacity (kVA)
14
25
47
88
110
Protective structure of the converter
Enclosed type (IP20)
Open type (IP00)
Cooling system
Forced air cooling
Approximate mass (kg)
7
12
24
39
53
Model name
FR-HC2-H
7.5
15
30
55
75
110
160
220
280
400
560
Applicable inverter capacity (kW)
7.5
15
30
55
75
110
160
220
280
400
560
Rated output capacity (kW)
11.0
20.2
37
73
92
135
192
264
336
476
660
Rated input voltage (V)
Three-phase 380V to 460V 50Hz/60Hz
Rated input current (A)
17
31
57
110
139
203
290
397
506
716
993
Overload current rating
150% 60s
Permissible power supply voltage
fluctuation
323V to 506V 50/60Hz
323V to 460V 50/60Hz
Permissible power supply
frequency fluctuation
5%
Input power factor
0.99 or more (when load ratio is 100%)
Power supply capacity (kVA)
14
26
47
90
113
165
235
322
410
580
804
Protective structure of the
converter
Enclosed type
Open type (IP00)
Cooling system
Forced air cooling
Approximate mass (kg)
9
9
26
43
37
56
120
120
160
250
250
HC2.book 148 ページ 2012年11月19日 月曜日 午前10時52分