33
2
Main circuit terminal specifications
<Reactor2 (FR-HCL22)>
For the 55K or lower, the cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible
temperature of 75°C. Assumes that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less.
For the 75K or higher, the recommended cable size is that of the cable (LMFC (heat resistant flexible cross-linked polyethylene insulated cable) etc.) with
continuous maximum permissible temperature of 90°C. Assumes that the surrounding air temperature is 50°C or less and wiring is performed in an
enclosure.
For the 30K or lower, the recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C. Assumes
that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
For the 55K or higher, the recommended cable size is that of the cable (THHN cable) with continuous maximum permissible temperature of 90°C. Assumes
that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in the United States.)
For the 30K or lower, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C. Assumes
that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
For the 55K or higher, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90°C. Assumes
that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in Europe.)
Screw size and tightening torque for earthing (grounding) are indicated in parentheses. (Refer to
page
for earthing (grounding).)
If a cable thinner than the recommended cable size is used, it may not be protected by the DC fuse. (Refer to
for the fuse selection.)
Model Name
Terminal
Screw Size
Tightening
Torque
N
m
Crimping
Terminal
Cable Size
HIV, etc.(mm
2
)
AWG/MCM
PVC, etc.(mm
2
)
R3/L13,S3/L23,T3/L33
R4/L14,S4/L24,T4/L34
R3/L13,S3/L23,T3/L33
R4/L14,S4/L24,T4/L34
R3/L13,S3/L23,T3/L33
R4/L14,S4/L24,T4/L34
R3/L13,S3/L23,T3/L33
R4/L14,S4/L24,T4/L34
FR-HCL22-H7.5K
M4
1.5
5.5-4
3.5
12
4
FR-HCL22-H15K
M5
2.5
5.5-5
5.5
10
6
FR-HCL22-H30K
M6
4.4
22-6
22
4
16
FR-HCL22-H55K
M8
7.8
60-8
60
1
35
FR-HCL22-H75K
M10
14.7
38-10
38
1
50
FR-HCL22-H110K
M10
14.7
60-10
60
1/0
50
FR-HCL22-H160K
M12
24.5
100-12
100
4/0
95
FR-HCL22-H220K
M12
24.5
150-12
150
300
150
FR-HCL22-H280K
M12
24.5
200-12
200
400
185
FR-HCL22-H400K
M12
24.5
C2-200
2
200
2
400
2
185
FR-HCL22-H560K
M12
24.5
C2-250
2
250
2
500
2
240