43
2
Wiring of main circuit (FR-HC2-H280K)
2.8.2
Wiring of main circuit
(1) Wiring power supply and reactor 1
Use the cable shown in the below table for the connection.
Use the moulded case circuit breaker (MCCB), the earth leakage circuit breaker (ELB) or the magnetic contactor (MC)
shown in the below table.
(2) Wiring reactor 1, filter capacitor, limit resistor, inrush current limit MC, and reactor 2
Cable gauge
200mm
2
Moulded Case Circuit Breaker (MCCB) or
Earth Leakage Circuit Breaker (ELB)
(NF or NV type)
700A
Magnetic Contactor (MC)
S-N600
MCCB
MC
Reactor 1
(FR-HCL21-H280K)
R/
L1
S/
L2
T/
L3
R2/
L2
S2/
L22
T2/
L32
Power
supply
Reactor 1
(FR-HCL21-H280K)
R2/
L12
S2/
L22
T2/
L32
R/
L1
S/
L2
T/
L3
Reactor 2
(FR-HCL22-H280K)
R4/
L14
S4/
L24
T4/
L34
R3/
L13
S3/
L23
T3/
L33
Limit MC
FR-HCC2-H280K
1) Filter capacitor
2)
3)
Converter
(FR-HC2-H280K)
thermostat output
Limit resistor (with thermostat)
0.96OHM BKO-CA1996H31
P/+
N/-
ROH
SD
To inverter
R4/
L14
S4/
L24
T4/
L34
Auxiliary contact for
limit MCs (NO contact) 3
∗1
∗1
∗2
∗3
∗3
∗3
∗3
∗3
∗3
Inrush current limit resistor
Connect the following devices to the appended terminal
block:0.96OHM BKO-CA1996H21 (without thermostat)
3
Inrush current limit resistor (only S-phase)
Connect the following devices to the appended terminal
block:
0.96OHM BKO-CA1996H21 (without thermostat)
2
0.96OHM BKO-CA1996H31 (with thermostat)
1
Appended terminal block and terminal block shorting
conductor