Parameter list
3.3 Parameter list
REMARKS
indicates simple mode parameters.
The parameters shaded in
allow their settings to be changed during operation even if "1" (write disabled) is set to
Pr. 77
Parameter write selection
.
Parameter
Name
Range
Increments
Initial
value
Refer to
page
Customer
setting
0
Simple mode selection
0, 9999
1
0
1
Maximum power supply frequency
60Hz (Read only)
60Hz
2
Minimum power supply frequency
50Hz (Read only)
50Hz
3
ROH terminal function selection
0 to 5, 9999
1
5
4
SOF terminal function selection
1
0
5
X1 terminal function selection
1
1
6
X2 terminal function selection
1
2
7
RES terminal function selection
1
3
8
SOF input selection
0, 1, 2
1
0
9
OH input selection
0, 1
1
0
10
RDY signal logic selection
0, 100
1
100
11
RSO terminal function selection
0 to 16, 98, 99, 100 to 116, 198,
199, 9999
1
1
12
CVO terminal function selection
1
2
13
Y1 terminal function selection
1
3
14
Y2 terminal function selection
1
4
15
Y3 terminal function selection
1
5
16
ABC terminal function selection
1
99
22
Current limit level
0 to 220%
0.1%
150%
23
Current limit level (regenerative)
0 to 220%, 9999
0.1%
9999
24
OL signal output timer
0 to 25s, 9999
0.1
0
25
Input current detection level
0 to 220%
0.1%
150%
26
Input current detection signal delay time
0 to 10s
0.1s
0s
27
Input current detection signal retention time 0 to 10s, 9999
0.1s
0.1s
28
Input current detection operation selection
0, 1
1
0
29
Zero current detection level
0 to 220%
0.1%
5%
30
Zero current detection time
0 to 1s
0.01s
0.5s
31
Life alarm status display
0 to 15 (Read only)
1
0
32
Inrush current limit circuit life display
0 to 100% (Read only)
1%
100%
33
Control circuit capacitor life display
0 to 100% (Read only)
1%
100%
34
Maintenance timer
0 (1 to 9998)
1
0
35
Maintenance timer alarm output set time
0 to 9998, 9999
1
9999
36
Cooling fan operation selection
0, 1
1
1
44
Instantaneous power failure detection signal
clear
0, 9999
1
9999
45
AM output filter
0 to 5s
0.01s
0.01s
46
Watt-hour meter clear
0, 10, 9999
1
9999
47
Energization time carrying-over times
Read only
1
0
48
Cumulative power monitor digit shifted
times
0 to 4, 9999
1
9999
49
Power supply frequency monitoring
reference
45Hz to 65Hz
0.01Hz
60Hz
50
AM terminal function selection
1 to 3, 5, 6, 7, 21, 1111 to 4444
1
1234
51
Input power monitoring reference
0 to 100kW/0 to 3600kW
0.01kW/
0.1kW
Rated
power
52
DU/PU main display data selection
0, 5 to 10, 25, 1111 to 4444
1
1234
53
Input voltage monitoring reference
0 to 500V
0.1V
220V/
440V
54
FM terminal function selection
1 to 3, 5, 6, 7, 21, 1111 to 4444
1
1234
55
Bus voltage monitoring reference
0 to 1000V
0.1V
340V/
680V