85
3
(2) Reference for input power monitor
(Pr. 51)
, input voltage monitor
(Pr. 53)
, bus voltage monitor
(Pr. 55)
,
and current monitor
(Pr. 56)
.
For the calibration of terminal FM, set the full-scale value of the connected meter when the pulse speed of terminal FM is
1440 pulse/s.
Set the power (kW), voltage (V) and current (A) to be indicated as the full-scale values to the frequency meter (1mA
analog meter) connected between terminal FM and SD.
Pulse speed is proportional to each monitor. (Maximum pulse train output is 2400 pulse/s. )
For the calibration of terminal AM, set the full-scale value of the connected meter when output voltage of terminal AM is
10VDC.
Set the power (kW), voltage (V) and current (A) to be indicated as the full scale values on the meter (10VDC voltmeter)
connected between terminal AM and 5.
Output voltage is proportional to each monitor. (Maximum output voltage is 10VDC.)
(3) Terminal AM response adjustment
(Pr. 45)
Using
Pr. 45
, the output voltage response of the terminal AM can be adjusted in the range of 0 to 5s.
Increasing the setting stabilizes the terminal AM output more but reduces the response level. (Setting "0" sets the
response level to 7ms.)
3600kW
0
Pr. 51
Initial setting (rated power)
500V
0
Pr. 53
Initial setting (220V(440V))
1000V
0
Pr. 55
Initial setting (340V(680V))
3600A
0
Pr. 56
Initial setting (rated current)
Setting range
2400
1440
3600kW
0
Pr. 51
Initial setting (rated power)
500V
0
Pr. 53
Initial setting (220V(440V))
1000V
0
Pr. 55
Initial setting (340V(680V))
3600A
0
Pr. 56
Initial setting (rated current)
Setting range
10VDC
Pulse speed (pulses/s)
Output voltage
HC2.book 85 ページ 2012年11月19日 月曜日 午前10時52分