18
ENGLISH
9.3.1.
Filter maintenance time setting
Set the filter maintenance display ON/OFF and time according to use.
2
3
4
2
3
4
3
4
3
4
When the accumulated operation time reaches the set time, indication
for filter cleaning is notified to the Remote controller.
After cleaning, press the filter button twice to reset the accumulated
operation time.
9.3.2.
Power-failure auto-recovery select
(independent of Fresh Master)
Set the Fresh Master operation condition when power failure is recov-
ered.
9
9
9.3.3.
Power ON feature
Set whether to operate the Fresh Master or not when the main power
is turned ON.
10
10
9.3.4.
Indoor unit and synchronous setting
Setting to synchronize with the indoor unit.
1
1
Maintenance time
Filter maintenance display ON
Filter maintenance display OFF*
1,500 hours
3,000 hours*
4,500 hours
Unrestricted
Switch
SW1
OFF
ON
Mode
Fresh Master stopped when power failure is
recovered.*
Fresh Master recovers to the prior state when
power failure is recovered.
Switch
SW1
OFF
ON
Mode
Inactive: operates according to the SW1-9
setting*
Active: operation starts with power ON
Switch
SW1
OFF
ON
9.3.5.
Humidifier mode select (GUF-50
•
100RDH3 only)
Setting the humidifier mode.
2
2
Used when operating only the Fresh Master and the temperature dur-
ing heating becomes too hot. The heating capability can be saved lower
temperature than normal.
9.3.6.
Heat operation stop temperature setting
(GUF-50 • 100RDH3 only)
Stopping the heating operation when synchronous with the indoor unit.
It becomes invalid when SW3-1 is ON.
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
3
4
5
9.3.7.
Exhaust fan operation setting
Setting the exhaust fan operation, although the supply fan will stop
when defrosting during heating or when withdrawing the refrigerant.
6
6
9.3.8.
Automatic humidifier control setting
(GUF-50
•
100RDH3 only)
Although the permeable-film humidifier is supplied with water for hu-
midifying when heating, there is a feature to automatically stop the
water supply depending on the outside temperature.
8
8
Mode
Synchronizing with the indoor unit*
Asynchronous with the indoor unit. The Re-
mote controller operation only.
Switch
SW3
OFF
ON
Mode
Standard humidifier mode*
Heat save humidifier mode (see below)
Switch
SW3
OFF
ON
Switch
SW3
OFF
ON
Set outside
temperature
6°C
7°C
8°C
9°C
OFF
ON
Set outside
temperature
10°C*
12°C
14°C
16°C
Mode
Exhaust fan in operation even when the sup-
ply fan is stopped*
Exhaust fan is stopped wen the supply fan is
stopped
Switch
SW3
OFF
ON
Mode
Automatic humidifier control prohibited*
Water is supplied to the permeable-film hu-
midifier constantly when the heater is in op-
eration.
Automatic humidifier control permitted
When the outside temperature is below 12°C
during heating operation, supply water to the
permeable-film humidifier.
Switch
SW3
OFF
ON
Summary of Contents for Fresh Master GUF-100RD3
Page 22: ...22 ENGLISH ...