B-52
FX Series PLC User's Manual - Data Communication Edition
N:N Network
9 Troubleshooting
9.6 Checking Absence/Presence of Data Transfer Errors
M: Master station, L: Slave station
*1.
Any slave station other than the slave station in which error occurred
*2.
Station in which error occurred
22H
Station number
error
L
L
*1
An unexpected slave station responded
to the sending request by the master
station.
Station number
settings
23H
Counter error
L
L
*1
The counter value included in the
parameter data is different from the
counter value given by a slave station.
Wiring
31H
Parameter not
received
L
L
*2
Before parameters had been received,
sending request was received from the
master station.
Wiring and power
supply
Error
code
Error name
Station
in which
error
occurred
Station
which
detected
error
Contents of error
Check point