C-36
FX Series PLC User's Manual - Data Communication Edition
Parallel Link
6 Test Run (Communication Test)
6.2 Creating Programs for the Communication Test
6
Confirming the link of the slave station
Set the PLC inputs (X000 to X003) to ON or OFF in the slave station, and confirm that the outputs
(Y000 to Y003) turn ON or OFF in the master station.
If unable to establish link, refer to "9. Troubleshooting".
6.2
Creating Programs for the Communication Test
Create the programs shown below for the master station and slave station.
6.2.1
For FX
2
(FX), FX
2C
, FX
1N
, FX
1NC
, FX
2N
, FX
2NC
, FX
3G
, FX
3GC
,
FX
3U
or FX
3UC
Series
1. Program for communication test (for the master station)
Create the program shown below for the communication test. (This program is not required during actual
operation.)
Set the inputs X000 to
X003 to ON or OFF.
Confirm that the outputs Y000 to Y003
of the slave station turn ON or OFF
according to the inputs of the master
station.
Master station
Slave station
M8000
M8070
MOV
K500
D8070
0
M8000
MOV
K1M900
K1Y000
11
MOV
K1X000
K1M800
22
END
M8000
M8178
(In the FX
3G,
FX
3GC,
FX
3U
and FX
3UC
)
This step is not required when using ch 1.
When using ch 2, set M8178 to ON.
8
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......