FX Series PLC User's Manual - Data Communication Edition
Computer Link
9 Related Data
9.2 Details of Related Devices
A
Comm
on I
te
ms
B
N:
N N
etwo
rk
C
Paral
le
l Li
nk
D
Com
puter Li
nk
E
In
verter
C
omm
uni
cation
F
N
on-Proto
col
C
ommunicati
on
(R
S/RS
2 Instru
ction
)
G
No
n-
Protoc
ol
Co
mmuni
ca
tion
(FX
2N
-2
32IF)
H
Programm
ing
Comm
uni
cation
I
Re
mo
te
Ma
intenance
Apx.A
D
isco
nti
nued
models
9.2.12 Time-out time setting [D8129 and D8429]
These devices set the evaluation time for error when receiving of data from the computer is interrupted.
1. Detailed contents
These devices set the error evaluation time in 10-ms units used when the receiving of data from the computer
is interrupted.
In all PLCs except FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs using the communication port, use D8129.
For FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs using the communication port ch1, use D8129.
Set the time-out time setting using parameters when using the communication port ch2 in FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs.
Use D8429 for confirmation.
The table below shows the setting range.
2. Cautions on use
Do not set the time-out time setting parameter and the time-out time (D8129) at the same time. The priority is
given to the parameter setting.
When setting the time-out time setting device (D8129) in an FX
0N
PLC, set the communication setting latched
(battery backed) device (M8120) to ON.
Make sure that the time-out time setting is not shorter than the time required to receive one character at the
set baud rate.
9.2.13 Operation mode display [D8419 and D8439]
These devices store the communication type being used. (in the FX
3S
, FX
3G
, FX
3GC
, FX
3U
and FX
3UC
)
1. Detailed contents
These devices store the code of the communication type currently being used in the communication port.
When communication port ch1 is used, D8419 stores the communication type.
When communication port ch2 is used, D8439 stores the communication type.
The table below shows the contents of the communication type codes.
FX Series
Setting range
FX
0N
, FX
1S
, FX
1N
, FX
1NC
1 to 255 (10 to 2550 ms) (When "0" is set, it is handled as "100 ms".)
FX
2
(FX), FX
2C
, FX
2N
, FX
2NC
,
FX
3S
, FX
3G
, FX
3GC
, FX
3U
, FX
3UC
1 to 3276 (10 to 32760 ms) (When "0" is set, it is handled as "100 ms".)
Code
Description
0
Programming communication
1
PP modem mode
2
Protocol dedicated to computer link
3
N:N Network
4
RS instruction
5
RS2 instruction
6
Parallel link
7
Inverter instruction
8
Variable analog potentiometer expansion board is used.
9
MODBUS communication
10
CF-ADP
11
ENET-ADP
12
Input/output expansion board is used.
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......