E-64
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
5 Communication Setting in Inverter
5.7 F700 and A700 Series (when built-in RS-485 terminal is connected)
5.7
F700 and A700 Series (when built-in RS-485 terminal is connected)
5.7.1
Contents of parameter setting
1. Contents of communication setting (essential items)
The table below shows parameters which should be set in all cases.
2. Parameters which should be adjusted between test operation and actual operation
3. Others (which should be set if necessary)
The table below shows parameters to be considered when using various system configuration and inverters.
For the method of use, refer to the respective inverter manual.
Parameter No.
Parameter item
Set value
Setting contents
Pr331
RS-485 communication station
00 to 31 Up to eight inverters can be connected.
Pr332
RS-485 communication speed
48
4800 bps
96
9600 bps (standard)
192
19200 bps
384
38400 bps
Pr333
RS-485 communication stop bit length
10
Data length: 7-bit/Stop bit: 1-bit
Pr334
RS-485 communication parity check
selection
2
2: Even parity
Pr337
RS-485 communication waiting time setting
9999
Set in communication data
Pr341
RS-485 communication CR/LF selection
1
CR: Provided, LF: Not provided
Pr79
Operation mode selection
0
External operation mode is selected when
power is turned ON.
Pr340
Communication startup mode selection
1
Computer link
Pr336
RS-485 communication check time interval
9999
Communication check is stopped.
Pr549
Protocol selection
0
Mitsubishi inverter (computer link) protocol
Parameter No.
Parameter item
Set value
Setting contents
Pr335
RS-485 communication number
of retries
9999
Set the value shown on the left during adjustment, and
set a value from 1 to 10 during operation.
Parameter No.
Parameter item
Set value
Setting contents
Pr342
Communication EEPROM write selection
0 or 1
0: EEPROM is written.
1: RAM is written.
Pr338
Communication operation command source
0 or 1
0: PLC
1: Outside
Pr339
Communication operation command source
0 or 1
0: PLC
1: Outside
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......