E-67
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
5 Communication Setting in Inverter
5.8 F800 and A800 Series (when built-in RS-485 terminal is connected)
A
Comm
on I
te
ms
B
N:
N N
etwo
rk
C
Paral
le
l Li
nk
D
Com
puter Li
nk
E
In
verter
C
omm
uni
cation
F
N
on-Proto
col
C
ommunicati
on
(R
S/RS
2 Instru
ction
)
G
No
n-
Protoc
ol
Co
mmuni
ca
tion
(FX
2N
-2
32IF)
H
Programm
ing
Comm
uni
cation
I
Re
mo
te
Ma
intenance
Apx.A
D
isco
nti
nued
models
5.8
F800 and A800 Series (when built-in RS-485 terminal is connected)
5.8.1
Contents of parameter setting
1. Contents of communication setting (essential items)
The table below shows parameters which should be set in all cases.
2. Parameters which should be adjusted between test operation and actual operation
3. Others (which should be set if necessary)
The table below shows parameters to be considered when using various system configuration and inverters.
For the method of use, refer to the respective inverter manual.
Parameter
No.
Parameter
group
Parameter item
Set value
Setting contents
Pr331
N030
RS-485 communication station
00 to 31 Up to eight inverters can be connected.
Pr332
N031
RS-485 communication speed
48
4800 bps
96
9600 bps (standard)
192
19200 bps
384
38400 bps
Pr333
—
RS-485 communication stop bit length/
data length
10
Data length: 7-bit/Stop bit: 1-bit
N032
RS-485 communication data length
1
Data length: 7 bits
N033
RS-485 communication stop bit length
0
Stop bit: 1 bit
Pr334
N034
RS-485 communication parity check
selection
2
2: Even parity
Pr337
N037
RS-485 communication waiting time
setting
9999
Set in communication data
Pr341
N038
RS-485 communication CR/LF selection
1
CR: Provided, LF: Not provided
Pr79
D000
Operation mode selection
0
External operation mode is selected
when power is turned ON.
Pr340
D001
Communication startup mode selection
1
Computer link
Pr549
N000
Protocol selection
0
Mitsubishi inverter (computer link)
protocol
Parameter
No.
Parameter
group
Parameter item
Set value
Setting contents
Pr335
N035
RS-485 communication number of
retries
9999
Set the value shown on the left during
adjustment, and set a value from 1 to
10 during operation.
Pr336
N036
RS-485 communication check time
interval
9999
Set the value shown on the left during
adjustment, and set a value in
accordance with the system
specification during operation.
Parameter
No.
Parameter
group
Parameter item
Set value
Setting contents
Pr342
N001
Communication EEPROM write
selection
0 or 1
0: Write to EEPROM and RAM.
1: Write to RAM only.
Pr338
D010
Communication operation command
source
0 or 1
0: PLC
1: Outside
Pr339
D011
Communication operation command
source
0 or 1
0: PLC
1: Outside
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......