E-100
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
9 Creating Programs (FX3S, FX3G, FX3GC, FX3U, FX3UC)
9.3 Common Items in Inverter Communication Instructions
9.3.3
Instruction completion and error flag operation
When two or more inverter communication instructions are programmed, the following flags turn ON or OFF
according to the execution result of each inverter communication instruction.
To acquire the result of each inverter communication instruction, make sure to provide these flags just below
each inverter communication instruction.
*1.
The IVBWR instruction is supported only in FX
3U
and FX
3UC
PLCs.
1. Operation of M8029 (instruction execution complete flag)
The operation of M8029 (instruction execution complete flag) represents the state in which the IVDR
instruction is completed while M0, M2 are off and M1 is ON.
2. Processing of communication errors
The following two types of processing are executed for communication errors.
The parity error/overrun error/framing error flags (shown in the upper column) turns ON when an error occurs
in any type of communication.
The error flag shown in the lower column turns ON when an error occurs during communication with an
inverter.
When inverter communication error flag turns ON, the step number is stored in the inverter communication
error occurrence step device (D8153 or D8158).
Create the program shown below for each corresponding instruction to check the inverter communication
error code (stored in D8152 or D8157).
Device
number
Description
Device
number
Description
ch1
ch2
ch1
ch2
M8029
Instruction execution complete
D8063 D8438 Serial communication error code
M8063 M8438 Serial communication error
D8152 D8157 Inverter communication error code
M8152 M8157 Inverter communication error
D8153 D8158 Step in which inverter communication error occurred
M8153 M8158
Inverter communication error
latch
D8154 D8159 IVBWR error parameter number
*1
M8154 M8159 IVBWR instruction error
*1
Bit device
Word device
Description
ch1
ch2
ch1
ch2
ch1
ch2
ch1
ch2
M8063 M8438 M8152 M8157 M8153
M8159 D8063 D8438
ON
OFF
OFF
6301
3801 Parity error, overrun error or framing error
ON
ON
ON
(only at first time)
6320
3820
Any inverter communication error other than
those above
M0
M1
M2
(OFF)
(ON)
(OFF)
Operation of
instruction execution
complete flag
M8029 : OFF
M8029 : ON
M8029 : OFF
FNC273
IVWR
FNC271
IVDR
FNC270
IVCK
[1] IVWR instruction is not driven
[2] IVDR instruction is driven
[3] IVCK instruction is not driven
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......