E-136
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
11 Troubleshooting
11.5 Checking Absence/Presence of Errors
11.5
Checking Absence/Presence of Errors
Verify that the error flag is not ON.
If the error flag is ON, check the error code and take proper countermeasures.
For error codes, refer to the next page.
11.6
Error Codes
When a communication error occurs, the error flag turns ON, and the error code is stored in the data register.
For error codes, refer to the table below.
1. Error storing devices
2. Error code list
FX Series
Error flag
Data register for storing error code
FX
2N
,FX
2NC
M8156
D8156
FX
3S
,FX
3G
,FX
3GC
,FX
3U
,FX
3UC
ch1
ch2
ch1
ch2
M8152
M8157
D8152
D8157
Error
code
(DEC)
Contents of error
Inverter
operation
0
Normal end
(No Errors)
1
Inverter did not give response.
2
Timeout error
Sending from inverter was aborted midway.
3
Station number error Unspecified station gave response.
4
Sum check error
The sum of data sent back by the inverter did not match.
5
Parameter number
specification error
In writing or reading a parameter, an improper parameter number
was specified.
At this time, error code (K6706) is set to D8067.
K6706: Out-of-range data value for operand in applied instruction.
6
Communication port
occupied by another
communication type
Because the port is being used for another communication type, it
cannot be used for communication with the inverter.
At this time, error code (K6762) is set to D8067.
K6762: The port specified in inverter communication instruction is
being used by another communication type.
7
Station number
outside setting range
A value outside the allowable range is set to the station number.
At this time, error code (K6706) is set to D8067.
K6706: Out-of-range data value for operand in applied instruction.
8
Sending timeout
error
*1
Sending to the inverter was not completed within the specified time.
9
Received data error
*1
Wrong data was received from the inverter.
256
Computer NAK error
Inverter sent the error code H0.
The number of retries exceeded the allowable number because of an
error in the transfer request data.
When errors
have occurred
consecutively
beyond the
allowable
number of
retries, inverter
is brought to an
alarm stop.
257
Parity error
Inverter sent the error code H1.
The contents are different from the specified parity.
258
Sum check error
Inverter sent the error code H2.
The sum check code in the computer is different from the sum value
calculated from the data received by the inverter.
259
Protocol error
Inverter sent the error code H3.
Syntax error is included in the data received by the inverter,
receiving of data was not completed within the specified time, or CR/
LF does not agree with the parameters.
260
Framing error
Inverter sent the error code H4.
The stop bit length is different from the initial set value.
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......