1. Outline
This chapter explains Non-protocol communication.
1.1
Outline of System
Non-protocol communication exchanges non-protocol data using a printer, bar code reader, etc.
In FX Series PLCs, non-protocol communication is available using the RS and RS2 instructions.
The RS2 instruction is dedicated to the FX
3S
, FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs.
In FX
3G
, FX
3GC
PLCs, the RS2 instruction allows communication using three channels at the same time.
In FX
3U
, FX
3UC
PLCs, the RS2 instruction allows communication using two channels at the same time.
1) Up to 4096 points of data can be sent, and up to 4096 points of data can be received. In the case of FX
2N
and FX
2NC
PLCs, make sure that the total number of sent and received data is 8000 points or less.
2) Data transfer is enabled when the connected equipment supports non-protocol serial communication.
3) The applicable total extension distance is 15m (49' 2") maximum in accordance with RS-232C
communication, and 500m (1640' 5") maximum in accordance with RS-485 communication [50m (164' 0")
when 485BD connection is used].
1. RS instruction
FX
2
(FX), FX
2C
, FX
0N
, FX
1S
, FX
1N
, FX
1NC
, FX
2N
, FX
2NC
, FX
3S
, FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs
....... For selection, refer to
Chapter 3.
Communication
equipment operating
in accordance with
RS-232C or
RS-485
Printer or bar code reader
FX PLC
RS-232C: 15 m (49' 2")/RS-485: 500 m (1640' 5")
[50 m (164' 0") when 485BD is used]
Total extension distance
For specifications,
refer to Chapter 2.
Bar code reader
or printer
Word devices
4096 points data
....... The amount of send data or
receive data can be 4096
points maximum.
For details, refer to Chapter 2.
....... For wiring, refer to
Chapter 4.
+
Transfer direction
....... To check applicable PLC
models, refer to Section 1.3.
In PLCs except for the FX
2N
, FX
2NC
, FX
3S
, FX
3G
, FX
3GC
, FX
3U
and FX
3UC
PLCs, the amount of send data or receive
data can be 256 points maximum.
Important points and reference
chapter/section
System
.......
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......