FX Series PLC User's Manual - Data Communication Edition
Non-Protocol Communication (FX
2N
-232IF)
2 Specification
2.1 Communication Specifications
2. Specification
This chapter explains the communication specifications.
2.1
Communication Specifications
Non-protocol communication type is used in the communication specifications shown in the table below.
Item
Specifications
Remarks
Transmission standard
RS-232C standard
Maximum total extension distance
15 m (49' 2")
Protocol type
Non-protocol communication
Communication method
Full-duplex, asynchronous system
Baud rate
300/600/1200/2400/4800/9600/19200 bps
Character
format
Start bit
—
Data bit
7-bit/8-bit
Parity bit
None, odd or even
Stop bit
1-bit/2-bit
Header
Provided or not provided
Up to four bytes can be
specified.
Terminator
Provided or not provided
Control line
Provided or not provided
Sum check
Provided or not provided