3. Outline of Communication Setting in the FX Series
This chapter describes which communication parameters can be changed for the following communication
types, and provides methods on how to change them.
• Computer link
• Inverter communication
• Non-protocol communication (RS/RS2 instruction)
• Internet mail sending
3.1
Setting Method
The following two communication setting methods are available for FX PLCs. Either method can be used, but
the method using parameters is recommended.
1. Setting methods
1) Specify the settings using parameters in the programming tool
Register the settings in parameters, transfer it to the PLC and turn the PLC's power OFF and then ON.
(This method is not available in FX
2
(FX), FX
2C
, and FX
0N
PLCs.)
(This method is not available for ch0 in FX
3G
, FX
3GC
PLCs.)
2) Directly specify the settings in a sequence program
Prepare a sequence program which sets the communication format, station number and time-out time
setting, and then transfer the program to the PLC.
Caution
Regardless of the method chosen above, a PLC operates the same way. If both methods are selected,
priority is given to the method using parameters.
2. Communication setting method availability in each FX PLC
*1.
Only ch1 and ch2 are available.
3. Setting flow
FX Series
FX
2
(FX),FX
2C
FX
0N
FX
1S
FX
1N
,FX
1NC
FX
2N
,FX
2NC
FX
3S
FX
3G,
FX
3GC
FX
3U
,FX
3UC
Parameter method
—
—
*1
Program method
Sequence
program for
set values
Parameter area
Program area
Parameter
method
Program
method
[MOV H
D8120]
[MOV K
D8121]
[MOV K
D8129]
[MOV H
D8400]
[MOV K
D8409]
[MOV H
D8420]
[MOV K
D8421]
[MOV K
D8429]
[MOV H
D8370]
[MOV K
D8379]
In FX
3S
, FX
3G
, FX
3GC
,
FX
3U
and FX
3UC
D8120
D8121
D8129
D8400
D8409
D8420
D8421
D8429
Communication format
Station number settings
Time-out time setting
Time-out time setting
Communication format
Communication format
Station number settings
Time-out time setting
Transferred
when power
is turned ON
Written by
program
ch1 Computer link
Ch0 is available only
in the FX
3G,
FX
3GC
PLC.
The setting method
using parameter cannot
be used for ch0.
Only ch1 is available
in the FX
3S
PLC.
RS instruction
Inverter communication
Programming communication
ch1 RS2 instruction
D8370
D8379 Time-out time setting
Communication format
ch0 RS2 instruction
ch2 Computer link
RS instruction
Inverter communication
Programming communication
Written by
program
Written by
program
Written by
program
PLC memory
When both methods are selected at the same time, priority is given to
the contents set using the parameter method.
Setting window
In FX
3S
, FX
3G
, FX
3GC
,
FX
3U
and FX
3UC
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......