B-66
FX Series PLC User's Manual - Data Communication Edition
N:N Network
10 Related Data
10.2 Details of Related Devices
10.2.18 Data transfer error code [D8211 to D8218] [D211 to D218]
These devices store the error code in the master station and slave stations.
1. Stations requiring program setting
The master station requires program setting.
However, this setting for the station itself is not required.
2. Detailed contents
1) The device used varies depending on the FX Series.
2) Error code list
M: Master station, L: Slave station
*1.
Any slave station other than the slave station in which error occurred
*2.
Station in which error occurred
3. Cautions on use
Data transfer sequence errors that occurred within the station itself cannot be detected.
Do not change the preset numeric value using a program or programming tool.
FX Series
Master
station
Slave
station
No. 1
Slave
station
No. 2
Slave
station
No. 3
Slave
station
No. 4
Slave
station
No. 5
Slave
station
No. 6
Slave
station
No. 7
FX
1N
, FX
1NC
, FX
2N
, FX
2NC
,
FX
3S
,
FX
3G
,
FX
3GC
, FX
3U
, FX
3UC
D8211
D8212
D8213
D8214
D8215
D8216
D8217
D8218
FX
0N
, FX
1S
D211
D212
D213
D214
D215
D216
D217
D218
Error
code
Error name
Station
in which
error
occurred
Station
which
detected
error
Contents of error
Check point
01H
Monitoring timeout
L
M
Slave station did not respond to the
sending request from the master station
within the monitoring time.
Wiring and power
supply
02H
Station number
error
L
M
An unexpected slave station responded
to the sending request by the master
station.
Station number
settings
03H
Counter error
L
M
The counter value included in the
parameter data is different from the
counter value given by a slave station.
Wiring
04H
Message format
error
L
M, L
The message given by the slave station
is incorrect.
Wiring, power
supply and station
number settings
11H
Monitoring timeout
M
L
The master station did not give a sending
request to the next slave station within
the monitoring timer.
Wiring and power
supply
14H
Message format
error
M
L
The message from the master station is
incorrect.
Wiring, power
supply and station
number settings
21H
Slave station no
response error
L
L
*1
The specified slave station does not exist.
Wiring, power
supply and station
number settings
22H
Station number
error
L
L
*1
An unexpected slave station responded
to the sending request by the master
station.
Station number
settings
23H
Counter error
L
L
*1
The counter value included in the
parameter data is different from the
counter value given by a slave station.
Wiring
31H
Parameter not
received
L
L
*2
Before parameters had been received,
sending request was received from the
master station.
Wiring and power
supply
Summary of Contents for FX-485ADP
Page 2: ......
Page 120: ...B 2 FX Series PLC User s Manual Data Communication Edition N N Network ...
Page 188: ...C 2 FX Series PLC User s Manual Data Communication Edition Parallel Link ...
Page 244: ...D 2 FX Series PLC User s Manual Data Communication Edition Computer Link ...
Page 344: ...E 2 FX Series PLC User s Manual Data Communication Edition Inverter Communication ...
Page 700: ...H 2 FX Series PLC User s Manual Data Communication Edition Programming Communication ...
Page 752: ...I 2 FX Series PLC User s Manual Data Communication Edition Remote Maintenance ...
Page 817: ......